You are using an outdated browser. Please update your browser now to display the page correctly.
Highly efficient circulation pump for heating and solar installations. There are different operating modes available for selection including PWM control enabling universal use. The pump is suitable...
All product information Scope of deliveryCE
Highly efficient circulation pump for heating and solar installations. There are different operating modes available for selection including PWM control enabling universal use. The pump is suitable for high temperatures and resistant to glycol mixtures.
Scope of delivery: | |||
1 x | pump | ||
2 x | Seal | ||
1 x | thermal insulation shell | ||
2 x | threaded pump connection 1" IT x 11/2╩ union nut | ||
1 x | PWM cable | ||
1 x | Connection cable 230 V | ||
Spare parts: | |||
![]() |
PWM cable for OEG circulation pumps |
|
|
![]() |
Connection cable for OEG circulation pumps |
|
For more information see Downloads
OEG no. | 512200103 |
Connection size: | 1 1/2" |
Nominal size [DN]: | 25 |
Total length [mm]: | 130 |
Delivery head [m]: | 7.5 |
Operating mode: | Automatic, Constant pressure, Constant speed, Proportional pressure, PWM signal |
Flow rate max. [m³]: | 3.4 |
Operating pressure max. [bar]: | 10 |
Warranty [years]: | 3 |
Media temperature [°C]: | 2 .. 110 |
Protection type [IP]: |
![]() IP44 ![]() |
Voltage [V]: | 230 |
Sound pressure level [dB]: | 42 |
Output [W]: | 60 |
Pumped medium: | Heating water, Water with up to 50 % glycol |
Plug type: | PWM: TE 166310-2 | TE 1879980-1, 230 V: Molex HX 45001-RT | HX 55001-3R |
Energy efficiency index: | 0.20 |
Manufacturer | OEG |
Brand | SilverTec® |
EAN | 4055668004361 |
Also replaces |
|
Weight [kg] | 2.5 |
Notes |
![]() CE ![]() |
Customs tariff number | 84136080 (CN) |
Please note that my email address at Automaxion is no longer working. PLEASE USE stephen.bysouth@gmail.com. I bought a 'circulateur-solaire-dn25-avec-commande-pwm-512200103' from you last year: N° de commande: 7465823 I was using this pump under PWM 2 control (with all LED's illuminated) and this worked well with my controller. In order to put the pump into PWM mode, I pressed the button for at least 5 seconds, as per the instructions. When I wanted to purge the system, I also would press the button for about 10 seconds to take it out of PWM mode and it would run continuously in the internally controlled mode. I was then afterwards able to put it back into PWM2 mode as before, for pressing for at least 5 seconds. Recently, I had to rework some of the system and I disconnected the pump from the mains power and then the controller to do the work. After I reconnected the system and the electrics, I purged the system (the pump was already not in PWM mode). However, now I cannot get the pump back into PWM mode. Pressing the button sequences through each internal mode at each button press, but holding the button in for at least 5 seconds (I have also tried 10 seconds) just continues to change the mode through the internal sequences and does not put the pump into PWM mode. In fact, sometimes this 5 second press, locks the mode into whatever internal mode it was before. Am I doing something wrong? Is there a way to restore it so that I can again get back the PWM 2 mode please? Thank-you in advance for your help,
Does the pump recognise a PWM signal, i.e. does the P-LED light up?
Because if not, the pump does not recognise the PWM signal and it cannot switch to PWM2 mode by pressing the mode button.
Nee, dit is helaas niet mogelijk
Sorry, beide kabels zijn inbegrepen.
Goedemorgen,
Ja de nieuwe versie van deze pomp is ook zonder PWM signaal te gebruiken
Ja, de charakteristieken zijn ook bij 100% water van toepassing.
Bonjour,
Non, ce n'est pas possible. Seulement avec le signal PWM.
Cordialement,
Votre équipe OEG
Spannung: PWM high Signal 4-24V (max. 10mA), PWM low >1V
PWM Signal 40- 4000Hz
bonjour, pouvons nous avoir le boitier electronique seul du circulateur 512200103
Bonjour,
Le boîtier électronique n'existe pas seul.
Il faudrait remplacer la pompe.
Cordialement,
Votre équipe OEG
ihre Art.Nr: 512200103 wird im Katalog als 8-Meter-Pumpe geführt, Online-Shop jedoch als 6-Meter-Pumpe beschrieben, welche Aussage ist richtig
Laut meiner Information gibt es von der Pumpe eine neue Serie, die jetzt bis zu 8 Meter Förderhöhe haben soll.
Gaan we naarleveren