The modular heating circuit K32 for heating systems controlled by a mixing valve. The connections of the heating circuit have an internal thread of 1". It also features large ball valve handles...
All product informationThe modular heating circuit K32 for heating systems controlled by a mixing valve. The connections of the heating circuit have an internal thread of 1". It also features large ball valve handles for easy handling and a visible closing position. The modular heating circuit is equipped with a design insulation with optimised function made of durable elastic EPP insulating the fittings 100%. Moreover, the system provides a ventilation opening to cool the pumps. Free access to the pump head is ensured by simply removing the front insulation shell. Additionally, the heating circuit provides a check valve (can be opened, 200-mm water column, spring-loaded) in the return pipe which prevents noise when electronically-controlled pumps are used, thus suited for horizontal and overhead installation. Standard installation of the flow is on the right, but flow and return line can be changed on site. All water-carrying parts are made of brass, the full-metal thermometer can be pulled off, with immersion sleeve integrated in the ball valve. The modular heating circuit is fully assembled with flat gaskets. The pump can be isolated, so no draining is necessary during service work.
Technical data:
- flat-sealing connections G 1½" ET
- dimension: DN 25 -1"
- fittings: brass
- gasket: EPDM / NBR
- insulation: EPP
- maximum pressure: 8 bar
- maximum temperature: 110° C
- kvs value: 4.4
- inlet (flat-seat): 1½" ET
- outlet: 1"IT
- centre distance: 125 mm
- installation length: 345 mm
- width of insulation: 250 mm
- height of insulation: 415 mm
- recommended range of application at Delta T =
temperature difference 20K up to 1,400 l/h: up to 32.5 kW
For more information see Downloads
OEG no. | 512244830 |
Suitable for pump connection size [inch]: | 1 1/2 |
Material: | Brass |
Seal: | EPDM, NBR |
Insulation: | EPP |
Operating pressure max. [bar]: | 8 |
Operating temperature max. [°C]: | 110 |
kvs-value [m³/h]: | 4.4 |
Connection boiler circuit: | 1 1/2" ET |
Connection heating circuit: | 1" IT |
Axial dimension: | 125 |
Length x Width [mm]: | 415 x 250 |
Weight [kg] | 2.4 |
Customs tariff number | 84818039 |
Bonjour,
Une pompe standard de 180 mm d'entraxe en 1 1/2'' FM est compatible.
Cordialement,
Votre équipe OEG
Que voulez vous piloter avec le groupe de pompe avec vanne 3 voie?
En principe:
Vous pouvez commander le servomoteur PAW
comme par exemple la KMS-D
Ou vous commandez la régulation WHMS et prenez le set de montage adéquat pour servomoteur PAW.
beim Modulheizkreis sitzt ein Mischer der Firma PAW drauf. Bei der WHMS ist im Lieferumfang eine Anbausatz für PAW-Mischer mit dabei. Jedoch braucht man hier noch den Ergänzungssatz Mischerwelle für PAW Mischer ( Artnr. Shaft adaptor for OEG actuator onto PAW mixer shaft)