You are using an outdated browser. Please update your browser now to display the page correctly.
Delivery the next working day
Right of return 14 days
mechanical
This mechanical boiler water low level alarm with welding socket DN 20 with float for closed heating systems according to DIN EN 12828 consists of a cast brass body with welding socket and...
mechanical
This mechanical boiler water low level alarm with welding socket DN 20 with float for closed heating systems according to DIN EN 12828 consists of a cast brass body with welding socket and a float mechanism, an electrical switch, test and manual reset buttons. TÜV tested as water level switch for max. operating pressure of 10 bar and a max. operating temperature of
120°C. Designed for heating systems according to DIN EN 12828. If the water level in the boiler drops below a minimum level, a float activates a switch which interrupts the power supply to the burner. A locking mechanism
prevents the burner from restarting automatically. The test button allows the float to be lowered to simulate a low water alarm condition.
Technical data:
Probe body: brass cast
Float: plastic
Installation height: 358 mm
Welding socket: DN 20
Max. operating temperature: 120°C
Max. operating pressure: 10 bar
Test pressure: 15 bar
Electr. connection: AC 250 V, 10 A
Protection class: IP 44
Approval: TÜV-HWB 02-232
WMS-WP 6-0, V-MS
- Like WMS-WP 6 but without locking mechanism. For use in systems where a remote control panel reset facility is provided.
WMS-WP 6-R2
- With external connection thread R2" for direct mounting to the boiler
For more information see Downloads
OEG no. | 512209841 |
EAN | 4016203423054 |
Weight [kg] | 2.88 |
Customs tariff number | 90261029 |